ASTM & AAMA water penetration testing

Vertix Diagnostics field-tests installed windows, doors, storefronts, curtain walls, sloped glazing, skylights, ribbon windows and exterior facades for water penetration, following written ASTM and AAMA test methods. We test for two reasons: quality assurance on new construction, and cause-and-origin investigation when water is already getting into a building.

We test and report; we do not install, seal or repair. An independent test is only worth something if the firm running it has no stake in the result, so the report goes to your general contractor, glazing subcontractor or envelope consultant to act on.

Infraspection Institute Certified Infrared Thermographer seal

Certified Infrared ThermographerASTM C1153-23 · ASTM E3216-26

ASTM International Member badge

ASTM International MemberASTM C1153-23 · ASTM E3216-26

AAMA 501.2: Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing Systems

What we test

Fenestration and facade assemblies, tested where they are installed.

A window can pass in a laboratory and still leak in the wall. Most field failures are not in the product itself but at the joint between the product and the building: the flashing, the sill pan, the perimeter sealant, the air barrier tie-in. Field testing checks the installed assembly, which is the thing that actually has to keep water out.

Our spray equipment is portable, so we test on occupied buildings, active job sites and upper floors reached by swing stage, lift or interior access.

  • Windows and ribbon windows
  • Exterior doors and sliding doors
  • Storefronts
  • Curtain walls
  • Sloped glazing and skylights
  • Exterior facades and cladding
  • Brick and masonry walls
  • Penetrations, transitions and perimeter joints

Two reasons to test

Prove it before turnover, or find it after it leaks.

New construction quality assurance

Baseline testing while the work is still open, so installation defects are caught by the trade that made them and corrected before finishes go in. Increasingly written into project specifications as a standard requirement.

Forensic cause & origin testing

For buildings that already leak: a controlled, simulated rainfall that reproduces the reported intrusion and isolates the exact point of failure, so the repair is scoped to the cause rather than the stain.

AAMA 501.2 field check

Professional AAMA 501.2 testing

AAMA 501.2, Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing Systems, is the hose-and-nozzle field test for glazing systems. Water is delivered through a calibrated brass nozzle at the pressure the standard specifies, confirmed on an inline gauge, and directed along one joint at a time for a set length and duration while an observer watches the interior. Because each joint is wetted on its own, a leak can be traced to a specific mullion, seal, corner or perimeter joint rather than to the whole system.

Storefronts

Mullion joints, glazing gaskets, door frames and the sill and perimeter joints where storefronts most often leak.

Curtain walls

Stack joints, vertical and horizontal mullion intersections, and anchor and perimeter conditions, tested from a swing stage or lift.

Sloped glazing & skylights

Rafter and purlin joints, glazing caps, curbs and flashing, with an observer inside watching the framing below.

QA or diagnostic

Run as a pass/fail quality assurance check on new installations, or as a diagnostic test to pin down an existing leak.

Water penetration testing services

The tests we perform.

Storefront water testing

Field testing of newly installed or existing aluminum storefront systems, entrances and their perimeter joints. Calibrated nozzle testing along mullions, glazing seals and sill details to AAMA 501.2, or spray rack testing with chamber pressure to ASTM E1105 where the specification calls for it, under the AAMA 503 field-testing framework.

Forensic water intrusion testing

Cause-and-origin testing for buildings that already leak. We reproduce the reported intrusion with calibrated spray equipment, isolating one component at a time until the entry point is found, following AAMA 511 and the ASTM E2128 approach to evaluating water leakage of building walls. Retesting after repair confirms the fix.

Masonry wall drainage testing

A cavity or drainage-plane masonry wall is designed to let some water in and drain it back out through flashings and weeps. Drainage testing checks that it does: water is introduced into the wall and we verify it exits at the weeps instead of reaching the backup wall or interior. Blocked weeps, missing end dams and mortar-filled cavities are the usual findings.

Facade testing

Water testing of exterior wall assemblies: curtain wall, window wall, panel and cladding systems, and the transitions between them. Spray rack testing of defined facade areas, paired with infrared scanning of the facade and interior to see where water travels inside the wall before it shows.

Brick wall water leak testing

Testing of brick and other masonry walls for water penetration through units, mortar joints, cracks and sealant joints. ASTM C1601 field testing measures how much water the wall surface absorbs and passes, separating porous brick and failed pointing from leaks at windows, copings and parapets. Common in New York brownstones, pre-war buildings and masonry facades.

Quality assurance & commissioning

Independent verification that the installation matches the specification.

Owners, architects and general contractors use an independent testing firm to confirm that windows, doors, storefronts and curtain wall were installed to the project specifications and to the manufacturer's installation requirements. A field test is the objective check: either the assembly holds water out at the specified test pressure, or it does not.

On new buildings we perform baseline water testing to confirm that openings and penetrations are properly flashed and sealed. A common sampling rate is around 20% of the fenestrations on a property, with the exact count and selection set by the project specification. Testing early in the installation sequence is the most valuable: a defect found on the first floor is corrected before it is repeated on every floor above.

The results create accountability. Each subcontractor's work is tested against the same written standard, failures are documented, and retesting confirms the correction before sign-off.

Typical QA sequence

  • Review of the specification and the test method it calls for
  • Selection of test openings with the architect or owner's representative
  • Testing at the specified pressure and duration, with interior observation
  • Pass / fail documented per opening, with photographs of any leakage
  • Retest of failed openings after correction
  • Written report for the project record and commissioning file

Our specialty

Water damage cause & origin investigations.

When a building is already leaking, the visible water marks where it came out, not where it went in. We use calibrated water spray rack equipment to recreate the reported intrusion in a controlled way, a procedure often called forensic water infiltration testing.

The method is systematic. Testing starts low on the assembly and works upward, wetting one component or joint at a time, so that when water appears inside it can be tied to a specific location. This matters because the source is often not the window everyone suspects: it can be the surrounding wall, a parapet or coping above, a sealant joint at the perimeter, or a cladding transition. Isolating each component is the only reliable way to separate them.

Every step is documented so the failure point can be repaired properly. Once the cause is identified, a scope of work can be written for your contractor. After the repair, we retest the same locations to verify that the intrusion has actually been stopped.

Where infrared fits in

  • Before testing: an infrared scan of the interior and facade narrows down where to test, so spray time goes to the likely locations.
  • During testing: the thermal camera shows water moving inside the wall before it reaches a finish, which shortens each test cycle.
  • After testing: moisture readings and thermal images record how far the water travelled, for the report and the repair scope.

Test methods

Which standard applies to your project.

AAMA (now part of the Fenestration and Glazing Industry Alliance, FGIA) and ASTM International publish the field test methods. The right one depends on the product, the project specification and whether the goal is acceptance testing or diagnosis. We will help you identify which method your specification calls for.

ASTM E1105Field water penetration of installed windows, skylights, doors and curtain walls, using a calibrated spray rack with a uniform or cyclic static air pressure difference applied by a test chamber. The most widely specified field test for new fenestration.
AAMA 501.2Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing Systems, using a calibrated nozzle and hose along joints and framing members.
AAMA 502Specification for field testing newly installed windows and doors, referencing ASTM E1105 for water and ASTM E783 for air leakage.
AAMA 503Specification for field testing newly installed storefronts, curtain walls and sloped glazing systems.
AAMA 511Guideline for forensic water penetration testing of fenestration products already in service, used in cause-and-origin investigations.
ASTM E2128Guide for evaluating water leakage of building walls: the framework for systematically investigating where and why a wall assembly leaks.
ASTM C1601Field determination of water penetration of masonry wall surfaces: measures water passing into brick and masonry walls through units, joints and cracks.
ASTM E783Field measurement of air leakage through installed exterior windows and doors, often run alongside water testing.

Test pressures, durations and pass/fail criteria are taken from the project specification and the current edition of the referenced standard. Field test pressures are often set at a reduced percentage of the product's laboratory rating, as the standard or specification directs.

Vertix certification

Standards behind our building diagnostics.

Water testing shows where an assembly fails under controlled conditions. Infrared thermography shows where water has already gone and how far it has spread. Vertix performs both, and our thermographic work follows these ASTM standards:

ASTM C1153-23Standard Practice for Location of Wet Insulation in Roofing Systems Using Infrared Imaging. The method behind our roof moisture surveys, used to map wet insulation after a leak and to define a targeted repair.

ASTM E3216-26Standard Guide for Use of Infrared Thermography in Evaluation of Buildings, Building Systems, and Equipment. The framework for planning, performing and reporting the thermal surveys that accompany our envelope and water intrusion work.

Credentials & equipment

  • Infraspection Institute Certified Infrared Thermographer
  • ASTM International Member
  • AAMA 501.2: Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing Systems
  • Calibrated water spray rack and nozzle equipment
  • FLIR E96 and T865 thermal cameras
  • Moisture meters for confirming wet material
  • Fully portable: we test anywhere in our service area

Our equipment →

What you receive

A test report that stands up on the project record.

The report is written so an architect can accept it, a contractor can act on it, and an owner or insurance carrier can rely on it.

  • The standard and test method used, with pressures, spray rates and durations
  • Location and identification of each opening or area tested
  • Pass / fail result for each test, or the isolated failure point in a forensic test
  • Photographs and, where useful, thermal images of any leakage
  • A clear description of the failure, written for your contractor to scope the repair
  • Retest results after correction, when retesting is part of the scope

Limitations, stated up front

  • A test shows performance on the day. It verifies the tested openings under the test conditions; untested openings are sampled, not proven.
  • Access sets the scope. Exterior access by lift or swing stage and interior access to the tested rooms must be arranged before the test date.
  • Weather matters. Testing is not run in freezing conditions or high wind, and real rain on the day can mask results.
  • Interior finishes may get wet. Forensic tests are designed to reproduce a leak, so we agree with you in advance how interior areas will be protected.
  • We do not open assemblies. Where the failure point is concealed, the report identifies where to open; your contractor does the opening.

Service locations

Where we perform ASTM & AAMA water testing

All five boroughs of New York City, Nassau and Suffolk counties on Long Island, northern and central New Jersey, and southwestern and central Connecticut. Each area has its own page.

Find us

Based in Hewlett, NY. Testing in NYC, Long Island, NJ & CT.

Our spray rack and test equipment is portable, so we come to the building. Vertix Diagnostics is based on Long Island and serves New York City, Long Island, northern and central New Jersey, and southwestern and central Connecticut.

Vertix Diagnostics
1208 W Broadway
Hewlett, NY 11557
(516) 234-5012
Sun–Fri 8 AM–8 PM · Sat closed

Common questions

ASTM & AAMA water testing — answered.

What is the difference between ASTM E1105 and AAMA 501.2?

ASTM E1105 uses a calibrated spray rack over the face of the assembly while a chamber applies an air pressure difference across it, simulating wind-driven rain. AAMA 501.2 uses a calibrated nozzle and hose directed along joints and framing members without a pressure chamber, and is typically used on storefronts, curtain walls and sloped glazing. The project specification normally states which one is required.

How many windows need to be tested on a new building?

The project specification sets the number. A common baseline is around 20% of the fenestrations on a property, with additional testing of any openings that fail and of their replacements. Testing the first installed openings early is the most cost-effective approach.

Can you find the source of an existing leak with water testing?

Yes. That is our specialty. We recreate the reported leak with calibrated spray equipment, testing one component at a time from the bottom up, until the water appears inside and the failure point is isolated. We then document it so a repair can be scoped, and retest after the repair to confirm it worked.

Can you test brick and masonry walls for leaks?

Yes. We perform brick wall water leak testing to ASTM C1601, which measures water penetration through the masonry surface, and masonry wall drainage testing, which checks that water entering a cavity wall drains out through the flashings and weeps instead of reaching the interior. Infrared scanning alongside the test shows where the water travels inside the wall.

Do you repair the window or the leak after testing?

No. We test and report; we do not install, seal or repair. That independence is why a general contractor, architect, owner or insurance carrier can rely on the result. The report goes to whichever contractor you choose.

Where do you perform water penetration testing?

Our equipment is portable. We test across all five boroughs of New York City, Nassau and Suffolk counties on Long Island, northern and central New Jersey, and southwestern and central Connecticut, on new construction sites and occupied buildings alike.

Why us and not a plumber

We write the report. We never bid the repair.

A plumber who finds your leak also sells you the repair. A roofer who inspects your roof also quotes the replacement. That isn't dishonesty — it's structure, and it quietly shapes every finding. We are an independent diagnostic company: we do not perform repairs, we do not sell materials, and we take no referral fee from any contractor. The report is the entire product, so there is nothing for us to gain by finding more than is there.

No repair revenue

We can't profit from the work we recommend, because we don't do the work. If your roof is 8% wet, the report says 8% — not "replace the field."

No referral fees

We accept nothing from contractors for sending work their way. Take our findings to your own plumber, roofer, or electrician, or put them out to bid.

Findings that carry weight

Boards, managing agents, and insurance carriers treat an independent finding differently than an estimate from the company that wants the job.

We'll tell you it's nothing

Sometimes the answer is condensation, or a warm duct, or a neighbor's roof. We're paid the same either way, so we say so.

Read why independence matters →

Request an inspection in your building